Explosion in a hydrogen production plant
The incident occurred at a hydrogen production plant, consisting of an electrolyser, a gasholder for the temporary storage of the hydrogen, compressors and gas dryers and final storage in four high pressure storage banks. Explosions occurred at different locations inside the hydrogen pipes feeding the high-pressure storage, causing the failure of welds and the connections at the storage system. These multiple confinement losses released hydrogen in large quantities from two of the four storage banks. The escaping hydrogen auto-ignited, resulting in an explosion and fire. The cause of the initial internal explosion was the formation and auto-ignition of an oxygen-hydrogen flammable mixture. The damage to the whole high-pressure section of the installation was considerable. No injuries.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The cause of the initial explosions was due to the spontaneous ignition inside the high-pressure feed pipes of an explosive mix of hydrogen and oxygen. The oxygen presence in the system was coming from the hydrogen electrolyser. The prime cause of it was blockages in the water feed lines to some electrolytic cells, allowing high levels of oxygen to mix with the hydrogen as electrolyte levels fell. The low-purity hydrogen was not detected by the low-pressure purity analyser due to a failure of the isolation transformer. The ROOT CAUSE can be attributed to an inadequate safety design of the installation and the lack of reliable online diagnostics which could have been able to provide the information on progressing deterioration of the hydrogen purity due to oxygen presence. Also the safe operation of the electrolyser lacked of proper performance detection.