In the acid treatment room of a Seveso low-threshold hazardous waste treatment centre, an explosion occurred on a 250 m³ concrete tank containing acid sludge being neutralized. The explosion occurred when the employee left the room and cut off the lighting of the building. The building was evacuated. The employee, severely burned, was transported to the hospital. Firefighters intervened. The concentration close to tank ceiling was 80% of the LFL. The operator filled the tank with water. The next day, the concentration was less than 10% of the LFL. The upper hatch of the tank was torn off. 30 m² of false ceiling were blown. The presence of H2 was suspected to be at the origin of the event. The company has never controlled this room so no reference explosion-related survey is available.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The presence of H2 was suspected to be at the origin of the event.