Explosion of flammable gases at the hydrocracker reactor of a refinery
A section of effluent piping ruptured on the hydrocracker reactor of a refinery. A mixture of light gases (methane, butane), light and heavy gasoline, gas oil and hydrogen was released from the pipe and instantly ignited upon contact with air, causing an explosion and fire. An operator who was checking a field temperature panel at the base of the reactor was killed; 46 employees or contractors were injured, 13 hospitalised. The effluent pipe ruptured because of excessively high temperature (over 760°C) stemming from catalyst bed. The excessive heat generated in a catalyst bed was initiated by a reactor temperature excursion that began with a hot spot in another bed (most likely caused by poor flow and heat distribution within the catalyst bed) and spread through the other beds. The excursion was not brought under control because the Stage 2 reactors were not depressurised and shut down as required when the reactor temperatures exceeded the 426°C temperature limit specified in the written operating procedures. Operators did not activate the emergency procedure because they were confused about whether a temperature excursion was actually occurring due to poor alarms (no additional audible high temperature alarm), fluctuating readings that obliged an operator to go read the temperature under the reactor.
Event Date
January 21, 1997
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The effluent pipe ruptured because of excessively high temperature (over 760°C) stemming from catalyst bed. The excessive heat was probably caused by poor flow and heat distribution within the catalyst bed. Accident and consequence were caused by a poor safety design and lacks in safety management.