Explosion at the chlorine electrolyser of a water treatment plant

The incident occurred at a tank of the chlorine electrolyser of a water treatment plant The plant products were sodium hypochlorite as a disinfectant for water treatments. The production process used was electrolysis of NaCl brines, which has hydrogen as by-products and has to be vented. Perhaps, the cause of this event was the erroneous closure of the hydrogen vent line, forcing the hydrogen gas into the liquid holding tank where it accumulated. During a maintenance stop, plant workers had drained the tank to within a few inches, to be able to repair a leak. They lowered then an electric pump into the tank to remove the remaining liquid. When the pump was switched on, the tank exploded.
Event Date
December 31, 1969
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the ignition of the hydrogen present in the NaCl tank. According to the investigation of the company CHEMAXX, the presence of hydrogen in the tank was probably due to the failure of or wrongly operated hydrogen venting system. The root cause is then probably a wrong procedure (ill-designed, or wrongly implemented).
Facility Information
Application Type
Application
Chlorine production
Specific Application Supply Chain Stage
Components Involved
water treatment plant, vent, NaOCl storage tank, pump, switch
Storage/Process Medium
Location Type
Location description
DESCRIPTION OF THE PROCESS The water treatment plant used an electrolytic process to generate sodium hypochlorite (NaOCl) from sodium chloride (NaCl). NaCl + H2O + ENERGY → NaOCl + H2
Operational Condition
Pre-event Summary
At the moment of the explosion maintenance works were ongoing on the NaOCl tank.
Consequences
Number of Injured Persons
0
Number of Fatalities
1
Investigation Comments

The main issues investigated by Chemaxx (company that carried out investigation) focused on the mechanisms and rates by which hydrogen gas is generated and subsequently accumulated in the holding tank. The need for active venting, warning signs and incidents of a similar nature were also reviewed.

Lessons Learned
The use of liquid sodium hypochlorite (NaOCl) instead of the more classic gaseous chlorine (CL2) had the advantage of handling a liquid, which is generally safer. The disadvantage was the production of hydrogen as a by-product of electrolysis. The hydrogen had then to be safely handled, for example by venting it to the atmosphere before the storage of the sodium hypochlorite in a tank.
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

originally a CHEMAXX investigation, not available anymore.

This event is also in H2TOOLS, https://h2tools. org/lessons/hydrogen-explosion-water-treatment-facility (accessed December 2025)

For an overview of the NaOCl process, incuding safety handling: Casson and Bess,On-Site Sodium Hypochlorite Generation,WEFTEC. 06 Conference of the Water Environment Federation - Oct. 21-25, 2006, Dallas, US