Explosion in a chemical storage unit
Two workers were asked to change the piping and support of a feed line into an intermediate storage vessel for hydrochloric acid. The explosion occurred when they opened the gas line and started grinding on the support,The flame propagated back into the tank, causing a second explosion inside. The explosion was caused by the unexpected presence of a considerable amount of hydrogen in the tank. According tot the eMARS and ARIA report (see references) , the hydrogen was formed in a reaction of metal powder traces and the hydrochloric acid, and must have accumulated over a period of two months. The metal powder was coming from the present in the supply line of the acid into the storage tank, as result of an incomplete reduction reaction in an upstream reactor. In that reactor, the metal powder was used to remove traces of metal oxides from the acid. Since 2009, the reactor was being operated at a lower temperature than the process was designed for, resulting in a lower reaction rate. Due to the lower reaction rate, traces of unreacted metal powder were present in the feed sent from the reactor to the intermediate storage vessel. In the storage vessel, the reaction continued, producing small amounts of hydrogen, which accumulated in the top. When the piping on top was opened, some hydrogen escaped and was ignited by the sparks of the grinding. The reactor has a ventilation system, designed to remove the hydrogen generated in the reduction reaction. The storage vessel did not.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING cause of the explosion was the accidental formation and later ignition of hydrogen in a chemical storage tank. As explained more in details in the lesson learned, the reason for the formation of hydrogen was a sequence of operative steps taking place before the storage along the process route, having major cause the decision to operate at a temperature lower than the design value. This suggest a lack of process control, inadequate risk assessment and consequently failing of putting in place the correct safeguards.