Explosion in a chemical plant
An explosion occurred at a plant where p-nitrophenol (PNP) is reduced to p-phenetidine with hydrogen. A drum supplying PNP to a hydrogen reduction reactor burst into flames, and part of the insulation was damaged and fell off. The upper part of the PNP drum and piping connecting the drum to the reduction reactor were destroyed by the fire. The explosion took place due to the convergence of several events. Workers did not firmly close a valve on discharge pipes of para-nitrophenetole (PNP) and forgot to close a valve fitted with an air-operated flow meter, so that hydrogen got into the PNP discharge pipes. With defects on the welded part of the pipes and corrosion by chlorine in PNP, the pipes got fractured to allow hydrogen to leak into the insulation cover of the PNP tank, where it accumulated to form explosive gas, which was ignited by electrostatic sparks generated when hydrogen was ejected.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

INITIATING CAUSE was the failure to perform two manual operations required before starting the reaction, allowing hydrogen to flow into the supply line of the product. CONTRIBUTING CAUSE was that this line was made of the wrong choice of the stainless steel material and affected by severe damage which caused its collapse. This damage was related to manufacturing defects and to the corrosion of the chemicals, which had already leaked in the past ROOT CAUSE is related to design shortcoming, lack of effective operative procedures and failure to learn from previous events.