Explosion and fire on a piping of a desulphurisation unit (83)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion and fire on a piping of a desulphurisation unit

At the time of the incident, the desulphurisation unit was shut down for scheduled cleaning of a cooling tower with reintroduction of a gas mixture into the system at a high hydrogen content. The accident was caused by the complete rupture of an 8″ heat-insulated carbon steel pipeline carrying a hydrocarbon/hydrogen mixture. It was located located along an upper rack. The event triggered an explosion whose pressure surge was evaluated by the site operator at approx. 60 mbar at a distance of 10 m. Since the leak was being fuelled, the following fire affected other pipelines as well as the exhaust valves connected to the flare system. This explains the persistence of several secondary fire outbreaks, finally extinguished 8 hours later. The quantities released were estimated by the operator to be less than 2 tonnes of liquid hydrocarbons and 50 kg of hydrogen.
Event Date
June 3, 2007
Record Quality Indicator
Region / Country
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was a leak on a pipe carrying hydrogen and hydrocarbons. The rupture was due to external corrosion localised on the pipeline supporting structure. Over a section approx. 45 cm long on the line’s lower half-circumference, the residual pipe wall thickness was in average 3 mm thick, while the original average thickness was 6. 5 mm. In some area the wall was think down to 1. 2 mm. The rupture occurred in two stages: an initial break, followed by propagation of the opening because of the high pressure of gases circulating inside the pipeline. A ROOT CAUSE is not provided by the source of this event. Nevertheless, from the corrective measures adopted, it can be deduced that the plant did not have effective inspection procedures able to detect degradation of the type occurred in the event. External corrosion is usually easy visible. However, it is very probable that the ruptured pipe was surrounded by thermal isolation layers. These not only hide any surface aggradation, but they may also as well contribute to the corrosion because of retainment of moistures.
Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved
pipe
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
The desulphurisation unit was stopped for a programmed clean-up of an aero-cooling with circulation of a hydrogen-rich mixture.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Currency
Property Loss (onsite)

2500000

Property Loss (offsite)

0

Post-event Summary

No victims were reported. The economic consequences were appraised at €500,000 of property damage and €2 million in production losses.

Event Nature
Emergency Action
The main fire was extinguished by the internal fire department after 50 minutes. As hydrogen leak was continuous, the fire extended to other pipes resulting in some secondary fires which were controlled after 10 hours.
Release Type
Release Substance
H2 50 kg hydrocarbons 200 kg
Hydrogen Release Concentration (%)
0.00
Release Amount (kg)
50.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event no. 33071 of the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/33071/ (accessed December 2020)