Explosion and fire at a diesel hydrogenation plant (1044)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion and fire at a diesel hydrogenation plant

The incident affected the raw material buffer tank (design pressure 0. 38 MPa) of a diesel hydrogenation unit in a refinery. This buffer tank is located between the hydrogenation reactor and the raw material storage tank. During pressure fluctuations in the lubricating oil system of a hydrogen compressor, the operator handled the situation improperly, resulting in an abnormal shutdown of the compressor, causing the hydrogen feed pump to interlock and stop. After the pump interlocked, the outlet valve was not closed in time and the two check valves failed. The high-pressure hydrogen gas in the system escaped into the tank. This caused an overpressure in the hydrogen buffer tank, which burst leading to a hydrogen-air explosion and a following fire, while diesel liquid spilled out to form a liquid pool on the ground.
Event Date
March 12, 2018
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause of the explosion was due to the tank being erroneously filled up with hydrogen. Part of the root cause sequence was the wrongful operations of the operator. However, if an operator executes a wrong action, the root cause could be lack of instruction, lack of training, or shortcomings in the design.
Facility Information
Application Type
Application
Diesel hydrogenation
Specific Application Supply Chain Stage
Components Involved
Hydrogen buffer tank, hdyrogen compressor
Storage/Process Medium
Design Pressure
0
Location Type
Location description
DESCRIPTION OF THE FACILITY The plant was producing (600,000 tonnes/year of diesel
Operational Condition
Pre-event Summary
The hydrogen compressor was experiencing pressure fluctuations in the lubricating oil system
Consequences
Number of Injured Persons
1
Number of Fatalities
3
Currency
Property Loss (onsite)

480000

Post-event Summary

2 fatalities, 1 injured person economic loss of about Euro 0. 48 million.

Event Nature
Release Type
Release Substance
H2, diesel
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Investigation report on the explosion of buffer tank.

B. Wang et al. , Hydrogen related accidents and lesson learned from events reported in the in east continental Asia,#2023, ICHS-2023

Liaocheng Anke News http://www. lcakzx. com/show. asp?id=798 (accessed Decemebr 2025)