Explosion and a fire at an ammonia production plant
The explosion occurred while restarting the ammonia reactor. Synthetic gas (70% H2) was released at the flange of the relief valve of the turbo-compressor. The explosion was followed by a jet fire. The hydrogen detectors and fire alarm notified the control room, triggering immediate shutdown of the facility. Rescue crews were quickly able to control the event.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause was the failure of the flange at a relief valve. Probably it had not been properly calibrated. While restarting the unit, this valve fluttered, causing vibrations that eventually led to rapid loosening of the flange nuts, which most likely had not been tightened enough at the outset. The inspection noticed also the lack of traceability of these jointing operations (torque). Considering also the difficulties encountered in the days before the accident, it could be concluded that repair/maintenance processes were part of the root cause.