European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre
Explosion at an ammonia plant (995)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Explosion at an ammonia plant
A release of "synthesis gas", containing primarily hydrogen occurred at the ammonia synthesis unt of a fertilisers plant. The location of the leak was a valve within the ammonia synthesis column. The gas, released at a pressure of 220 bar and a temperature of 120°C, ignited spontaneously, forming two flame cones directed along the pipe connected to the valve. The pipe did not resist the heat from these flames and 15 minutes later burst under internal pressure freeing its contents, which in turn exploded. The quantity of gas released during the accident was estimated at 1. 45 tonnes. The gas continued to burn for more than two hours, given the quantities found at the site when the fire broke out. The consequences of this accident however remained confined to the zone adjacent to the valve. Two workers were slightly injured when they were trying to isolate the valve. This accident was caused by a gas leak on the joint between the body and cap of a shut-off valve on a pipe transporting synthesis gas. The valve, in the open position, was operating at full flow. The seal between the two parts, held together by 12 bolts, was applied to a metal-on-metal contact. Inspection of the valve indicated that gas had leaked in two spots prior to ignition, meaning that two distinct flames were produced.
The INITIATING CAUSE was the loss of confinement of a shut-off valve, due to inadequate sealing of th flange surface. The investigation revealed several anomalies: (1) inadequate clamping of nuts, the subcontracted firm did not follow any pre-established set of procedures or specifications in conducting this operation. (2) degraded surface of the valve seal surfaces: a sizeable lateral surface groove, presence of particles of a shape and composition analogous to those of shot blasting material used to clean metal surfaces. The ROOT CAUSES were inadequate execution of maintenance on the valve and lack of proper management of contractors’ operation by the site operator.
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.
Contact info
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.
The INITIATING CAUSE was the loss of confinement of a shut-off valve, due to inadequate sealing of th flange surface. The investigation revealed several anomalies: (1) inadequate clamping of nuts, the subcontracted firm did not follow any pre-established set of procedures or specifications in conducting this operation. (2) degraded surface of the valve seal surfaces: a sizeable lateral surface groove, presence of particles of a shape and composition analogous to those of shot blasting material used to clean metal surfaces. The ROOT CAUSES were inadequate execution of maintenance on the valve and lack of proper management of contractors’ operation by the site operator.