Skip to main content

Explosion in a aluminium manufacturing plant (1251)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Explosion in a aluminium manufacturing plant

An explosion occurred at the fume treatment unit of a foundry. The fumes contained chlorine, used in the metal treatment process. The treatment unit function by spraying water and caustic soda. The facility was put in safe mode and the furnaces containing metal were shut down. Restarting the furnaces was subject to approval by the classified installations inspectorate.

Event Date
January 27, 2024
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The event was probably due to the reaction between the residues in the extraction ducts and the caustic soda, which caused a release of hydrogen. A similar event had occurred at the site seven years earlier, which had been attributed to the excessive presence of metallic dust in the unit, which in contact with water produced hydrogen (See HIAD_1250 based on ARIA 50150). At that time, several improvements were introduced to the treatment unit, to be able to monitor and detect earlier the conditions under which hydrogen is accidental produced.

Facility Information
Application Type
Application
Aluminium processing
Specific Application Supply Chain Stage
Storage/Process Medium
Storage/Process Quantity
0
Actual Pressure
0
Design Pressure
0
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Property Loss (onsite)

low

Event Nature
Release Type
Release Substance
H2 NaOH aluminium dust
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Event nr 61581 of the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/61581/ (accessed December 2025)