Explosion in a aluminium manufacturing plant
A explosion occurred in the gas and dust treatment system for the aluminium holding furnaces at a metallurgical plant. The explosion caused the failure of the treatment system, the operation of the production lines without gas treatment resulted in the release of chlorine and chlorinated compounds into the atmosphere, as well as dust containing aluminium and zinc particles in various chemical forms.
Event Date
May 6, 2017
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences

The INITIATING CAUSE of the explosion was a buildup of dust in the holding furnaces' suction ducts. This metallic dust reacted with the caustic soda at the base of the column, producing hydrogen. These same hot particles were the IGNTION SOURCE, by providing the activation energy necessary to ignite the hydrogen. These materials are composed of aluminium and zinc in their metallic form, as well as oxides, hydroxides, and various salts. They react with water, and this reaction is amplified in the presence of caustic soda and at high temperatures. This phenomenon had not been detected in the risk assessment, and therefore they were not considered in the safety provisions of plant operations.