Conventional fire on a CGH2 trailer
Early in the morning a hydrogen tube trailer experienced a tire fire and pulled onto the road shoulder. The driver attempted to extinguish the fire with the fire extinguisher on the vehicle. Heat from the fire caused seats on the isolation valves of two tubes to deform and the welded stainless steel manifold to crack, releasing hydrogen, ignited then by the tire fire. The driver was unable to extinguish the fire and called the emergency number. Emergency responders closed the highway in both directions for several hours. There were 2 injuries, the material damage was limited to the trailer.
Event Date
February 12, 2011
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was a conventional fire on tire following brake failure. The ROOT CAUSE can be probably related to ageing of the tires or of the brake system. Maintenance procedures are in palce to avoid these azards. Morevoer, tube protection from conventional fires seems having been not very effective (design shortcoming).