Ammonia-hydrogen explosion in a pulp production plant
The incident occurred at a pulp mill plant producing fluting media. The explosion took place at a pulp storage tank and was caused by the combustion of a hydrogen-ammonia gas mixture. The roof of the pulp storage tank was detached due to the pressure generated in the explosion, and it landed on to the roof of the adjacent mill building, which partially collapsed. Bacterial strains producing hydrogen had formed in the white water and pulp storage tanks of the mill before the accident. The conditions in the pulp storage tank were favourable for them, and hydrogen was released into the air in the tank. The residual ammonia produced in the process was in a gas form under the conditions of the pulp storage tank, so that hydrogen and ammonia gas to form a flammable gas mixture. The gas mixture was most likely ignited by a spark from static electricity because no other ignition sources were identified in the pulp storage tank. The accident did not cause any personal injury, but material damage/ The production was halted for approximately six weeks.

The INITIATING CAUSE was the accidental generation of hydrogen by bacteria in the pulp storage. Considering that (1) the possibility of hydrogen formation is known, and (2) that the plant had been modified and since then was affected by ROOT CAUSE could be identified in some (1) shortcoming in designing preventive and mitigating measures and (2) proper management of the challenges related to the introduction of a new process.