Accidental production of hydrogen and fire in a silicone manufacturing plant
The event occurred in a silicon hydride (SiH) emulsion production process inside an enclosed production building. The reaction was ongoing when one of the tank started overflowing with foam. The process generated a flammable gas cloud gas ignited, which later ignited causing an explosion and fire. The shift supervisor ordered to open the garage doors and to turn on forced ventilation to remove the hazy vapour which had started to form. Before these two actions could take place, the explosion took place. At the time of the incident there were nine employees onsite. . The explosion caused four fatalities and one injured worker, heavily damaged the production building and its force was felt up to 20 miles away. According to the CSB preliminary report, various investigations are still ongoing to understand in details the sequence of events of this accident. The most plausible explanation is that the flammable mixture (hydrogen) has been generated by the run-away of a chemical reaction when producing the SiH emulsion. Short before the start of the accidents, the reactor tanks were seen producing a large quantities of foam, typically induced by bulk production of hydrogen in viscous liquids.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause of the event was the production of a flammable mixture (very probably hydrogen) and its delayed ignition during a chemical reaction process. Contributing cause were the absence of flammable gas detectors or hydrogen gas detectors able to warn workers. Also the position of the main air mover near the process location and the decision to open the door of the building to remove smoke increased the potential of explosion from flammable gases. The root cause is very probably to be found in the absence of preventive and mitigating measures tailored to that specific chemical process. This implies an inadequate risk assessment.