Accidental formation and ignition of hydrogen due to corrosion
This event occurred at a theatre building. A contractor was conducting routine maintenance on a dry pipe sprinkler system in the basement of the theatre. By opening the pipe, an explosion occurred that caused burn injuries to the contractor. The investigation concluded that the accident has been caused by hydrogen released into the sprinkler room from the sprinkler piping, when opening the sprinkler system. The released hydrogen formed a flammable mix with the air and ignited. It is known that hydrogen forms in galvanised steel pipes, as a corrosion reaction product between zinc coating, oxygen from air and water. The investigation could not identify the exact cause of the ignition.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING CAUSE was the production of hydrogen from corrosion of zinc galvanic coating with oxygen and water. The IGNITION CAUSE is unknown. But is plausible to assume that it came from a spark of the tools used by the maintenance contractor. The ROOT CAUSE was the failing to foreseeing the possibility of hydrogen formation and to take the required preventing / mitigating measure