Yes, small flowrate vents may be invisible, particularly in daylight. Sometimes it may still be possible to see heat striations in the air from the heat generated by the fire, but it can be difficult to discern at low flowrates. 

Category: Properties
Keywords: Vent, Flame, Flow

This may be able to be accomplished as a method for ignition. We have not seen it.

As flaring is not usually recommended, especially when timing is an issue, a sparker that takes time to ignite would not be recommended.

Category: System Design

A vent system should still be installed in case the flare system does not remain ignited.  

Category: System Design

Typical practice for gaseous tube trailers is to vent relief devices independently to the top of the vehicle. This is primarily to accommodate the large flowrates and high thrust forces involved from these releases. It’s fairly easy to do this since the vent lines are fairly short due to the maximum road height of trailers. Regulations do not prohibit piping multiple devices into a
single…

Category: System Design

A release is defined by the amount of hydrogen, the rate of hydrogen flow, vent location (indoors or outdoors), geometry in the area (confined or not), and pressure. 

A small or large release should be differentiated by the damage that can occur because of an ignition. This can be a fire, deflagration, or detonation.

Therefore, the relative size of the release will vary based…

Category: System Design
Keywords: Release, Vent

Low-pressure vents at mostly low hydrogen purity are not as large safety risk as high-pressure pure hydrogen vents. These vents should still go to a vent stack, but it will probably be small in diameter and thus the tee vent at the top can be small.

If the purge requires high flow, if purging horizontally, the reaction forces of the flow exiting and the hydrogen cloud should be modeled…

Category: System Design

Delayed ignition is a significant hazard for hydrogen releases, either intended or unintended. The primary concern is the overpressure and energy release created from a vapor cloud which could contain a significant quantity of hydrogen. The H2Tools Incidents database contains a number of examples of delayed ignition. 

  1. Understand any reactions the hydrogen can add to what is being vented. For instance, O2/H2 vented in the same stack would not be a good idea.
  2. Understand all the flow and operating parameters of the streams to ensure no back flow into the hydrogen system or vice versa.
  3. Ensure the venting/flaring system can handle the hydrogen flow parameters.
Category: Miscellaneous
Keywords: Vent, Flaring

Liquid hydrogen will almost never accumulate in a vent system since vent systems are typically designed without insulation. The extremely cold liquid hydrogen temperature of -420 F.

Additionally, vent stacks on an LH2 tank are connected to the vapor phase of the tank. Only in a few rare instances will LH2 be entrained in the gas stream.

Accumulators are recommended at the bottom of…

Category: System Design

The deflagration pressure is dependent upon many variables.

However, some general concepts are:

  1. Deflagration pressure is proportional to operating pressure
  2. Deflagration pressure is inversely related to initial temperature
  3. Deflagration pressure is based on concentration and H2/O2 ratio
  4. In general, an internal deflagration is unlikely to exceed about a 10…
Category: System Design