Yes, for all stacks. GH2 has a minimum prescriptive height of 10 ft. There is no minimum prescriptive height for LH2. However, 25 ft has been a best practice for the industry for years. Vent stack…
Hydrogen vent stack fires can create NOx. While not typical, certain municipalities will require air permits to address the emissions from hydrogen flare systems, and even from intermittent…
At NASA Cape Canaveral, they used a natural gas line connected to the vent stack outlet with a thermal sensor to make sure the pilot was lit. They may also have had a sensor to ensure the H2 fire…
A vent system should still be installed in case the flare system does not remain ignited.