In laboratories, 316 stainless steel tubing is frequently the first choice for small flow and pressures less than 2800 psi (19 MPa). See Best Practices: Material Compatibility for hydrogen compatibility with various materials. Always work within manufacturer’s pressure ratings adjusted for temperature. Read and follow…

Category: System Design

Rupture discs open very rapidly. Historically, rupture discs opening at high pressure (1000 psig and above) have caused the most damage due to deflagration/detonation. Timing a rupture disc would not be possible. Additionally, how would you have a pilot light on a moving tube trailer? Even with a pilot light at the end of the stack may blow out due to the initial high velocity.

See…

Category: System Design

Vent stacks must be designed for a fire at the outlet. The mesh is designed to ensure no blockage of the vent stack by animals/insects. 

Additionally, the mesh must be designed for pressure drop to ensure code-compliant back pressure on the relief devices.

Category: System Design

Yes, numerous incidents have occurred where frozen air (which contains oxygen) has built up within a hydrogen process or vent system. These incidents with vent systems incorporate more than just a vent stack, but include a vent system consisting of additional atmospheric equipment (such as a tank) where the equipment stays cold and allows air into the system in contact with a cold hydrogen…

Category: System Design

Heat tracing can be used as a safeguard against freezing. However, it must be understood that: 

  • The heat trace system uses a utility supply so may not always be operational.
  • The electrical equipment must be properly classified for the area, which can be challenging for the Div 1 classification for vent stack outlets.
  • The heat tracing might be damaged by vent…
Category: System Design

Hydrogen flames can be nearly invisible in daylight, especially at low flowrates. The concentration of hydrogen does not have much effect on the color of the flame. Many hydrogen incidents or fires will have a bright orange hue, or even yellow flames. The color is primarily caused by contaminants that is either naturally in the air in certain environments, swept into the air during the release…

Category: Properties
Keywords: Fire, Flame

Hydrogen vent stack fires can create NOx. While not typical, certain municipalities will require air permits to address the emissions from hydrogen flare systems, and even from intermittent ignition of vent stacks. This is highly dependent on the location and interpretation of regulations. A hydrogen flare system is much more likely to require an air permit than a standard vent system.

Category: System Design
Keywords: Flare, Vent Stack

Flame arrestors can be installed on hydrogen gas vents. The purpose of a flame arrestor is to prevent the migration of flame backwards and upstream into the vent stack or system itself. Generally, flame arrestors are not needed since: 1) the vent stack should be designed to withstand fire or explosion within the stack, and 2) the process generally does not contain a flammable mixture within it…

Category: System Design

Welded joints are always best, but they cannot always be used as a connection to tanks and tubes, as mechanical joints are needed for maintenance. Supports for the reaction forces can help ensure the mechanical joints in the piping does not pull apart. 

If large diameter or thick-walled tube is installed with compression fittings, the use of hydraulic swaging is recommended.

…
Category: System Design

There are many designs of storage systems where multiple vessels might be needed to obtain the required storage quantity. Regulations differ between vessels and modules which are intended for stationary or transportation purposes. Similarly, there are differences in codes globally. The issues of requiring shutoff valves on individual vessels and requiring TPRD’s are linked since generally…

Category: System Design