No, but it depends on the application. Nearly all vents less than 4” in size are not purged with N2. This is primarily due to: 1) large flows required to dilute hydrogen below the flammable range,…
AICHE ELA253 CHS ” Introduction to Hydrogen Safety for First Responders” is a good reference and discusses both LH2 and GH2. LH2 fires are very unusual. LH2 releases usually are GH2 so the fires…
The vent system should be designed for the temperature at which it operates (ambient for GH2 and Cryogenic for LH2). The outlet of the vent system should be designed for a fire to ensure the…
Heat tracing can be used as a safeguard against freezing. However, it must be understood that:
Yes, for all stacks. GH2 has a minimum prescriptive height of 10 ft. There is no minimum prescriptive height for LH2. However, 25 ft has been a best practice for the industry for years. Vent stack…
Nearly all hydrogen storage tanks and hydrogen storage systems will need some type of pressure relief system to protect the vessels from overpressure. If there are pressure relief devices, some…
There is no specific requirement not to vent liquid hydrogen from a vent system. Best practice would be to only vent gas from the top of the vessel to relieve pressure. If liquid must be vented,…
Spraying water onto a vent stack, either for gaseous hydrogen or liquid hydrogen, is not recommended. While this is prohibited within the code for liquid hydrogen due to the much greater hazard of…