There is no specific requirement not to vent liquid hydrogen from a vent system. Best practice would be to only vent gas from the top of the vessel to relieve pressure. If liquid must be vented, it should be vaporized first. 

Note: It is very unusual to have LH2 flow from a liquid tank out the vent system, as the vent system is connected to the vapor space on the LH2 tanks and there…

Category: Miscellaneous

Design of vent header lines is critical to the safety of the system. From a process perspective, the pipe design must be sufficient to withstand back pressure, thrust forces from the flow, and must be of a sufficient size to not create a restriction that prevents proper flow or activation of the devices. Per ASME BPV Code requirements, backpressure should be limited to no more than 10% of the…

Category: System Design

At NASA Cape Canaveral, they used a natural gas line connected to the vent stack outlet with a thermal sensor to make sure the pilot was lit. They may also have had a sensor to ensure the H2 fire was lit. In cases where substantial quantities of unused hydrogen is vented and the timing and amount of the flow rate is known and controlled, flaring might be useful. NASA guidelines stipulate that…

Category: System Design

I am not sure which picture you are referring to so I will attempt to answer.

If you are referring to the incident where a fire occurred and the vent system was damaged, then this may have been due to lack of proper supports and incomplete assembly of the test systems. In the past, vent systems were not pressure tested for strength but that is changing. 

If you are talking…

Category: Miscellaneous

No, in nearly all cases, a deluge system is not needed. The proper sizing of relief devices using documents such as CGA S1.3 will ensure that they are of sufficient size to address worst case scenarios. In addition, if the system has been sited per separation distances from exposures in accordance with documents such as NFPA 2, then there should not be a significant risk of fire
exposure.…

Category: System Design

There is no standard which specifically specifies the use of a flapper. A properly designed flapper should provide de minimus restriction to vent flow, yet still provides weather protection which allows for a vertical release of the vent stack flow, which is best from a dispersion and radiation perspective. Flappers are extensively used successfully and safely on nearly all liquid hydrogen…

Category: Miscellaneous

There are no differences in the process design of the vent stack since the venting requirements will follow the same sizing and pressure rating requirements regardless of vent configuration. However, vent systems often create liquid air on their exterior due to the cold venting temperatures. Since this liquid air will drip off the stack, it should be diverted such that it does not directly…

Category: System Design

Flame arrestors can be installed on hydrogen gas vents. The purpose of a flame arrestor is to prevent the migration of flame backwards and upstream into the vent stack or system itself. Generally, flame arrestors are not needed since: 1) the vent stack should be designed to withstand fire or explosion within the stack, and 2) the process generally does not contain a flammable mixture within it…

Category: System Design
Keywords: Vent, Flame Arrestor

The main advantage of a “tee” style design is that the thrust loads at the vent exits are balanced. This means that an unequal force that might push the vent stack over is not present. Generally, the tee is also of the same size as the main vent line, thereby doubling the vent area for less pressure drop. The main disadvantage of a tee stack is that they generally vent with a horizontal…

Category: System Design

All vent stacks/systems should be bonded and grounded to minimize ignition sources. Higher pressure streams from higher velocities have a greater risk of igniting for several reasons, including particle impingement. Adding mesh could create more impact points for particulate, which would increase the potential for ignition, but would not increase the probability of a DDT. Similarly, high flow…

Category: Miscellaneous