Heat tracing can be used as a safeguard against freezing. However, it must be understood that: 

  • The heat trace system uses a utility supply so may not always be operational.
  • The electrical equipment must be properly classified for the area, which can be challenging for the Div 1 classification for vent stack outlets.
  • The heat tracing might be damaged by vent…
Category: System Design

Purging is not recommended as a continuous part of vent stack operation. However, maintenance activity is a transient event and it’s prudent and recommended to purge a vent system prior to performing maintenance. It’s always possible that hydrogen could be leaking internally from a valve or other component and therefore create a hazard. Of particular note, care must be taken that proper…

Category: Miscellaneous

We are not aware of a study for blended NG/H2. However, for high concentrations of NG, the vent system should be similar to NG, which still recommends a vent system as NG is less dense than air. For nearly pure hydrogen the recommendations of this presentation are in effect.

Category: Miscellaneous

Hydrogen vent stack fires can create NOx. While not typical, certain municipalities will require air permits to address the emissions from hydrogen flare systems, and even from intermittent ignition of vent stacks. This is highly dependent on the location and interpretation of regulations. A hydrogen flare system is much more likely to require an air permit than a standard vent system.

Category: System Design
Keywords: Flare, Vent Stack

Flame arrestors can be installed on hydrogen gas vents. The purpose of a flame arrestor is to prevent the migration of flame backwards and upstream into the vent stack or system itself. Generally, flame arrestors are not needed since: 1) the vent stack should be designed to withstand fire or explosion within the stack, and 2) the process generally does not contain a flammable mixture within it…

Category: System Design

Welded joints are always best, but they cannot always be used as a connection to tanks and tubes, as mechanical joints are needed for maintenance. Supports for the reaction forces can help ensure the mechanical joints in the piping does not pull apart. 

If large diameter or thick-walled tube is installed with compression fittings, the use of hydraulic swaging is recommended.

…
Category: System Design

There are many designs of storage systems where multiple vessels might be needed to obtain the required storage quantity. Regulations differ between vessels and modules which are intended for stationary or transportation purposes. Similarly, there are differences in codes globally. The issues of requiring shutoff valves on individual vessels and requiring TPRD’s are linked since generally…

Category: System Design

We are not certain what an inverted vent top is. If this means the hydrogen flow is pointed downward in any way towards grade, then yes it must be avoided. Less dangerous vent gases can be pointed downward, especially those that mix with air rapidly (nitrogen/oxygen/argon). Regardless, reaction forces must be taken into account for any relief valve activation or flow.

Category: System Design
Keywords: Flow, Vent, Relief valve

Nearly all hydrogen storage tanks and hydrogen storage systems will need some type of pressure relief system to protect the vessels from overpressure. If there are pressure relief devices, some means to vent the hydrogen to a safe location will be needed. An exception to this is hydrogen cylinders due to their relief device type (lead-backed rupture discs (CG-4/5) and
the need to transport…

Category: System Design

The distances provided are minimums. While they might be sufficient for most vents from small systems, larger vents will require both a dispersion and radiation analysis to determine the height needed.

Category: System Design
Keywords: Flow