Syngas fire at a shift catalyst reactor (319)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Syngas fire at a shift catalyst reactor

There was a small leak of syngas (a mixture mainly consisting of hydrogen and carbon monoxide) resulting in a localised fire at a bolted flange joint on the outlet carbon steel pipework of the High Temperature Shift Catalyst Vessel.
Event Date
November 23, 2007
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

INITIATING CAUSE The cause of the leak at the flange was probably caused by a leaking gasket.

Facility Information
Application Type
Application
Ammonia production
Specific Application Supply Chain Stage
Components Involved
High Temperature Shift Catalyst Vessel.
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Event Nature
Emergency Action
The incident was identified and quickly brought under control by initiating a controlled shutdown of the plant where the flame size was reduced and ultimately extinguished. It was not considered necessary to initiate the plant Emergency Shutdown procedure. The leak occurred at an elevated and un-occupied position on the vessel. Since the leak occurred in the in the "hot front end" of the plant, a controlled the cool down was necessary, for 24 hours, after which the gasket could be replaced. The restart took around 36 to 48 hours.
Release Type
Release Substance
H2, CO
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description provided by HSE, original source confidential