Syngas fire in in a chemical plant
The event occurred while re-starting the ammonia production unit after a technical stop, a synthesis gas (50% hydrogen, 17% ammonia, methane and nitrogen) leak ignited on a flange located just after the synthesis reactor. Emergency shutdown of the unit was executed and the fire was extinguished in a bit less than 1 hour. The leaking at the flange was caused by a tightening torques of the bolt which were not adapted to the exceptional conditions prevailing during the accident. The short technical breakdown had induced a very quick temperature evolution with significant temperature gradients between the bolts and the flange.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was loss of tightness of the flange due to the temperature gradient occurred during the technical shutdown. flange were not adapted to the situation. The ROOT CAUSE (or at least an intermediate cause) is related to the fact that these temperature excursions had not been taken into account in the design of the reactor. Assuming that the operation of tightening had been executed by a contractor during the last inspection and maintenance works, another factor of the ROOT CAUSE could be the management of the contractor's operation by the site operator.