rupture LH2 tank
The incident occurred on a large LH2 stationary storage tank at an aerospace testing facility. The cryogeninc tank experienced a significant vacuum leak in the insulation annulus, which eventually led to major cracks in the bottom of the outer shell. Two rupture disc assemblies at the top of the tank developed leaks and a pressure rise was noted in the annular space. However, due to the need to perform incumbent rocket engine test, it was decided to continue the operation of the tank instead of removing it from service. A normal liquid top-off induced a cryo-pumping resulting in the drop of the annular space pressure from approximately 9332. 6 Pa to 3. 1 Pa. During test runs, operational constraints were implemented to prevent shifting and damage of the inner vessel. After completion of the test, the tank was drained to facilitate repair of the leaking rupture disk assemblies. However, two days after the tank had been completely emptied, heavy frost developed on the bottom of the outer vessel. Temperature sensors indicated the outer tank wall was less than 90 K at the bottom, which is well below the ductility range for its carbon steel outer wall. Additional vacuum pumping was attempted but proved difficult due to small port sizes and/or perlite intrusion into the pumping system. Eighteen days after tank drain, the outer vessel cracked.

The INITIATING CAUSE was the development of cracks at joints in the outer shell, which caused air entrance into the insulating vacuum shell. The ROOT CAUSE was manufacturing error and the choice of low strength steel for the material of the outer shell.