Rupture of a heat exchanger in a refinery, due to hydrogen attack
A petroleum refinery experienced a catastrophic rupture of a heat exchanger in the catalytic reformer / naphtha hydrotreater unit. The heat exchanger catastrophically ruptured because of High Temperature Hydrogen Attack. Highly flammable hydrogen and naphtha at more than 500 degrees Fahrenheit (260ºC) were released from the ruptured heat exchanger and ignited, causing an explosion and an intense fire that burned for more than three hours. The accident fatally injured seven employees (one shift supervisor and six operators) who were working in the immediate vicinity of the heat exchanger at the time of the incident.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING CAUSE was carbon steel degradation and seal break due to high temperature hydrogen attack (HTHA). The reports speak of self-ignition of the naphtha/H2 mixture. Because of the refinery’s long history of frequent leaks and occasional fires during this start-up activity, the CSB considered this work to be hazardous and non-routine.