Release of a pressure release valve

A hydrogen safety sensor went into alarm at a hydrogen demonstration facility. The early morning temperature was near freezing and there was a trace of precipitation on exposed surfaces. Upon further inspection following the sensor alarm, a 3,500 psig (approximately 24 MPa) stationary storage vent was found to be releasing hydrogen through the PRD vent stack (PRD = Pressure Relief Device). The alarming sensor was at an adjacent building but responded to hydrogen 20 yards (18 m) downwind from the vent location. The vent release location is 10 feet (3 m) above ground level. No ignition was detected. [Source: Burgess et al. , Technical Report NREL/TP-5400-67381]
Event Date
November 1, 2014
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
Review of pressure data did not show a pressure above the PRD set point. Freezing temperatures and moisture are suspected as contributing factors to spurious opening of the valve. Once the valve popped open, the cold temperatures of the escaping gas could have caused the valve to freeze in the open position. Freezing and ice forming are regularly reported as causes for the malfunctioning of safety devices. Inspection and maintenance should be designed according to the related risks.
Facility Information
Application Type
Application
hydrogen laboratory
Specific Application Supply Chain Stage
Components Involved
PRD, vent stck
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
The early morning temperature was near freezing and there was a trace of precipitation on exposed surfaces.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

N

Property Loss (offsite)

N

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Burgess et al. , Technical Report NREL/TP-5400-67381 https://www. nrel. gov/docs/fy18osti/67381. pdf (accessed August 2024)