Release in a nuclear power plant
A hydrogen release occurred in a storage area of a nuclear power plant. . The storage consisted of three trailers made of 14 compressed gas cylinders each. The cylinders, mounted horizontally, had a nominal working pressure of 200 bar, and were all connected to the same line supplying hydrogen to the workshop. The rupture of a faucet nut of one of the cylinders started the release. Since all the cylinders were connected to the same connector, the rupture induced the discharge of the all hydrogen stored: 2275 Nm3, without igniting.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause of the accident the mechanical failure of a faucet nut on one of the cylinders, triggered by a stress corrosion cracking. The nut was made of brass. The root or intermediate cause was a less than optimal design of the nut. An inspection performed one year before, foreseen every three years, had not identified any abnormal situation . A cause contributing to the aggravation of the consequence was that the whole storage content was connected without safeguards to one supply pipe. The report failed in identifying this aspects. .