Skip to main content

Release of hydrocarbons and hydrogen in a refinery (901)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Release of hydrocarbons and hydrogen in a refinery

The accident occurred on one of the heat exchangers of the hydro-desulphurisation unit. The role of the exchanger , located between the charge pumps and the furnace, was to heat the charge using the hot products from the reactor. Before the exchanger, pressurised hydrogen is injected into the charge. The exchanger was equipped with interchangeable bundles mounted with deflector plates. During a shutdown, some beams were mistakenly reassembled upside down. When the installation restarted and the compressor of the hydrogen circuit arrived at 75% of its capacity, one of the deflectors was blown off and obstructed the inlet of the exchanger. Consequently, the safety device of the compressor triggered the compressor stop and the pressure release valves released part of the contents.
Event Date
January 31, 1984
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The reason for the over-pressurisation of the compressor and the pressure relief activation was the block of part of the gas flow into the heat exchanger tubes bundle. A ROOT CAUSE component was a human error occurred when re-installing the exchanger's components inverted. However, an additional factor was the failure of the supervision and final inspection procedure to detect the mistake.

Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved
heat exchanger
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
The desulphurisation unit was restarted after a shutdown during which component of the heat exchanger unit were (wrongly) reinstalled
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

Part of the hydrocarbon load, including hydrogen, was released to the environment.

Event Nature
Release Type
Release Substance
H2, hydrocarbons
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Original description of the event in database ARIA