Release of a flammable mixture from a compressor
Following the breakdown of a piston rod, a mixture of hydrogen and light hydrocarbons was released from the fresh hydrogen compressor of an oil refinery. The rod broke down because of stress corrosion. The stress exerted on the rod was significantly increased by the looseness of the piston fixing point. The gas mixture ignited, also igniting the lubricating oil and other items in the room. Some 1,500 kg of hydrogen gas and a few hundred litres of lubricating oil were estimated to have been burned.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The IMMEDIATE CAUSE was the breaking rupture a rod due to stress corrosion. The stress exerted on the rod was significantly increased by the looseness of the piston fixing point. The ROOT CAUSE, although not provided by the source, could be identified in shortcomings in service and maintenance. Nevertheless, also a design error cannot be excluded.