This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Release at a dispenser of a HRS

Minor leak in the break-away coupling for 35MPa dispenser of a refuelling station for buses. The leak developed in the break-away coupling during a controlled test refuel. The test was attended by the station operator’s staff. The leak occurred as the temperature was decreasing (the hydrogen is pre-chilled to between -33oC and -40oC prior to entering the dispenser). The dispenser was taken out of service until a replacement break-away coupling was installed by the manufacturer. The 70MPa dispenser remained operational. The dispenser system had been leak-tested during the installation/commissioning phase, however this had only been carried out at ambient temperature. It is believed that the leak was only present at low temperature.
Event Date
May 25, 2016
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments

Shortcoming in the testing procedure did not allowed for the detection of a small leak.

Facility Information
Application Type
Application
HRS
Specific Application Supply Chain Stage
Components Involved
break-away
Storage/Process Medium
Actual Pressure
35
Design Pressure
35
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

The 35MPa dispenser was taken out of service until a replacement break-away coupling was installed by the manufacturer. The 70MPa dispenser remained operational. No injury or harm to any people.

Lessons Learned
Leak test at ambient temperature may not be sufficient to identify leaks within systems cooled during normal operation. It is proposed that a leak test is conducted during commissioning at the minimum temperature expected during operation. A more refined automated leak detection logic needs to be developed and is under discussion with the manufacturer in order to capture this type of leaks when trained personnel are not present.
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Report provided but confidential