Release at a dispenser of a HRS
Minor leak in the break-away coupling for 35MPa dispenser of a refuelling station for buses. The leak developed in the break-away coupling during a controlled test refuel. The test was attended by the station operator’s staff. The leak occurred as the temperature was decreasing (the hydrogen is pre-chilled to between -33oC and -40oC prior to entering the dispenser). The dispenser was taken out of service until a replacement break-away coupling was installed by the manufacturer. The 70MPa dispenser remained operational. The dispenser system had been leak-tested during the installation/commissioning phase, however this had only been carried out at ambient temperature. It is believed that the leak was only present at low temperature.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

Shortcoming in the testing procedure did not allowed for the detection of a small leak.