Release from a bulk hydrogen storage (324)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Release from a bulk hydrogen storage

Approximately 250kg hydrogen gas released from vent stack following failure of a relief valve on bulk hydrogen installation. No ignition and no injuries. The system had been recently installed. It was equipped with a number of pressure relief controls. This controls were designed to be able to handle in various ways hydrogen overpressure situations. At first, the main regulator was opening at a cylinder pressure exceeding 8. 6 bar; it was closing again at 9. 7 bar. Above this pressure, a relief valve was opening at 10. 5 bar releasing the hydrogen via a feed pipe to the process. If this operation was failing to relieve the pressure, a second relief valve was opening at 12. 5 bar and the hydrogen was vented to the atmosphere via a stack. Finally, a pressure relief valve (PRV) activating at 16. 5 bar represented the ultimate system protection. In the case of this incident, the second relief valve opened but did not re-closed correctly, probably because of the freezing of the valve seat. This caused an uncontrolled release of hydrogen to the atmosphere. The situation was quickly recognised and steps were taken to stop the release. During the release, a 5 mm pipe connecting the second relief valve to the vent snapped due to the shock caused by the hydrogen pressure wave.
Event Date
September 26, 1997
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

INITIATING CAUSE The uncontrolled hydrogen release to the atmosphere was caused by a relief valve failure to re-close, possibly due to freezing. CONTRIBUTING CAUSE The hydrogen released by this valve was supposed to be discharged to the environment via a vent duct. However, the connection between the valve and the vent failed. ROOT CAUSE The failure of the valve has been related to its possible freezing. This suggest an ill-design, related to the choice of a wrong component unable or to failing to consider all occurring environmental conditions during operation. Also the snapping of a pipe due to the shock wave of the release is due to ill-design. [NOTE of HIAD Validator: the pressure control system is not well described by the sources, so that it is impossible to assess its design-soundness in term of safety. ] .

Facility Information
Application
hydrogen storage
Specific Application Supply Chain Stage
Components Involved
vent stack, pressure relief valve, pipe.
Storage/Process Medium
Actual Pressure
0
Design Pressure
0
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

0

Property Loss (offsite)

0

Post-event Summary

250 kg of hydrogen released to the atmosphere, but they did not ignite. No injury, no damage.

Event Nature
Emergency Action
The situation was quickly recognised and steps taken to stop the release. The reference does not specify which steps.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Release Amount (kg)
250.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description provided by HSE, original source confidential