LH2 valve leaking at a research centre

This near miss affected a testing installation for liquid hydrogen. A leak was located on a valve installed on a purge line connected with a LH2 storage tank. This shut-off valve served to discharge hydrogen into the exhaust stack of the installation, in case LH2 evaporation from the filling or withdrawal hose was causing excessive pressure. It was also serving a purging purpose, by flushing the filling hose with gaseous hydrogen before filling the cylinder with LH2. The valve was more than 20 years and was not sealing properly under cryogenic conditions, causing hydrogen gas to escape from the threated connection between the valve stem and the valve case. The valve failed on two internal parts: the metal diaphragm and the O-ring that served as a seal (a sealing with thoric geometry). The metal diaphragm no longer seated properly against the valve seat causing leakage.

Event Date
June 3, 2025
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Facility Information
Application Type
Application
LH2 stationary tank
Specific Application Supply Chain Stage
Components Involved

tank, piping

Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Property Loss (onsite)

low

Property Loss (offsite)

NO

Post-event Summary

A new valve and a new piping system ahd to be installed.

Event Nature
Emergency Action

none required

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Infrmation provided by project leader by email (6 October 2025) - CONFIDENTIAL