leaks from a threaded joint
At a hydrogen production facility, hydrogen stored in a 40 MPa hydrogen storage unit leaked from the main body of a fitting of the storage pressure and flow control system. The leak was not detected by the fixed hydrogen safety detector but discovered by safety officer using a portable gas detector during a routine tightness test. By using soap water, the officer located the leak near the main cone-and-thread type fitting of the 40 MPa gas accumulator unit. The safety personnel stopped the use of the 40 MPa gas storage unit and depressurised the piping system.
Event Date
June 4, 2020
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was a leak in a threaded joint of the hydrogen storage control system. The facility had already experienced three leak events on the same component, which had been replaced with another of the same producer, model and batch. The investigations following previous leaks had identified that an initial defect in the joint manufacturing process had progressed due to hydrogen embrittlement, leading to the leaks. However, despite corrective measures, additional leaks occurred on 11 May and 4 June 2022. Various hypotheses were formulated: hydrogen embrittlement, hydrogen erosion, pitting corrosion, fatigue cracking, stress corrosion cracking and non-metallic inclusions. Based on microstructural observations and of the operative conditions, the study concluded that the first 5 hypotheses were unlikely and determined that the leak was caused by non-metallic inclusions. It was assumed that many non-metallic inclusions remained in the base material during the fabrication, and the interfaces between the non-metallic inclusions and the base material represented crack onsets due to stress concentration, leading to the leak. Based on these findings, it can be concluded that the ROOT CAUSE was lack of manufacturing quality and control.