Skip to main content

Leak Fir from the a hydrogen flange in a synthetic adhesives production plant (633)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Leak Fir from the a hydrogen flange in a synthetic adhesives production plant

This accident occurred at the unit producing synthetic adhesives by adding hydrogen to petroleum resin under high temperature and pressure. Hydrogen was added to the reaction via a supply pipe at the bottom of the reactor. Hydrogen leaked from a flange of the check valve attached to the hydrogen supply pipe and ignited due to static electricity. The leak was due to the deformation of the flange gasket, made of aluminium. The aluminium had deformed due to the high temperature, reducing the tightness of the flange.
Event Date
July 7, 1986
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the deformation of the gasket of a flange on the hydrogen supply pipe. The KHK report attributes the ROOT CAUSE to the wrong choice of the gasket material. The report does not specify if this was due to a wrong installation (human error) or a lack of clarity of procedures.

Facility Information
Application Type
Application
resins production
Specific Application Supply Chain Stage
Components Involved
gasket, flange, check valve,
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
1
Number of Fatalities
0
Post-event Summary

minor injury

Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

High Pressure Gas Accident Cases Database of the KHK (High Pressure Gas Safety Association): https://www. khk. or. jp/public_information/incident_investigation/hpg_incident/incident_db. html (accessed May 2025)