Hydrogen release from a liquid hydrogen truck
The truck was carrying 25 m3 of liquid hydrogen and was parked in the parking lot of a road restaurant. The hydrogen escaped through the safety devices of the tank and then dispersed (the weather was wet and there is fog). Technicians from the charter company degassed the tank until the leak stopped, then escorted the truck to a technical centre. A crack in the inner tank causing a pressure build-up could be the cause of the accident.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
According to the ARIA report, the INITIATING CAUSE was a crack in the inner tank was the probable initiating cause. The has probably caused liquid hydrogen leaking into the annular vacuum space, evaporating an caused a pressure build-up in triggering the over-pressure safeguard.