Hydrogen release from a hydrogen pipeline (478)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Hydrogen release from a hydrogen pipeline

Alarm received by firefighters around midnight by a resident who heard abnormal noise under the Beaumont Bridge while walking his dog. Perimeter of security set up very quickly with isolation of the section. Pipeline was depressurised within the hour. The pipeline was completely emptied and purged with nitrogen. A security perimeter was established in the night from Sunday to Monday, around 1 am and raised around 5 o'clock. The police banned access to several main arteries of the old town all night, and the inhabitants were confined to their homes. Reparation was done during the next day and were validated in the night. No significant impact on customers.
Event Date
May 6, 2019
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING CAUSE was the loss of confinement of the pipeline. This is usually related to local corrosion, which could start from the inside wall of the pipe (for example tiggered by hydrogen-steel interaction) or could be induced from outside, for example by chemical process in the ground around the pipe, or by external solicitations such as mechanical vibrations from traffic. The statistics related to gas leaks shows that this second type of damage is the most frequently causing gas releases. For the ROOT CAUSE two alternative factors could be identified: a materials defect already existing in the as-manufactured pipe component, and/or a lack of maintenance allowing the corrosion to progress beyond an allowed degree of damage
Facility Information
Application
Pipeline
Specific Application Supply Chain Stage
Components Involved
pipeline
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

No impact on person, no material loss. The police banned access to several main arteries of the old commune all night, and the inhabitants were confined to their homes. Reparation is done, improve maintenance frequency

Event Nature
Emergency Action
1. Alarm received by firefighters around midnight Sunday. 2. A security perimeter was established in the night from Sunday to Monday in Marchienne-au-Pont (west of Charleroi). 3. The police banned access to several main arteries of the old town all night, and the inhabitants were confined to their homes. 4. Pipeline was depressurized within the hour, completely emptied and purged with nitrogen. 6. Reparation was done during the next day and were validated by NoBO in the following night.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Hole Shape
Hole Diameter (mm)
2
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

News from Sud Info

News by DHNet https://www. dhnet. be/regions/charleroi/2019/05/06/le-centre-de-marchienne-au-pont-boucle-pour-fuite-dhydrogene-F23QSNVLIZEULBMSEW2AKVZTL4/ (accessed June 2024)