A hydrogen leak at a 70 MPa dispenser
This event occurred at the hydrogen 70 MPa dispenser of a refuelling station during the testing phase. Just after the start of the refuelling test, at a pressure of approximately 13 MPa, the hydrogen gas leak detection alarm inside the main body of the dispenser went off at 4% of the LEL, triggering the to shut down of the whole the hydrogen refuelling station. Using a portable hydrogen gas detector to identify the leak location, workers discovered that the leak had originated from a joint inside the dispenser. There were no injuries or property damage. The leak occurred during the first filling operation after a safety inspection of the hydrogen station. The leak location was at a threaded joint on the direct filling compressor side, immediately upstream of a hand valve. This is the chronological summary of the actions performed before the leak occurred: (1) 13 days before the leak, during a regular inspection, an engineering company subcontractor performed an airtight test on the dispenser piping, but only from the downstream side of the direct-filling compressor to the hand valve. The test was done with hydrogen at 82 MPa for 15 minutes. No leak was found. (2) The day after, the dispenser manufacturer retightened some of the fittings inside the dispenser in, but again only downstream of the hand valve for maintenance inside the dispenser. This retightening work that was not specified in the work instructions. It is believed that the fitting in question loosened, when another fitting was being retightened. The fittings in question were not retightened. (3) After the retightening, the company conducted an airtightness test, but due to a misunderstanding of the scope of the airtightness test, the fittings in question and the retightened fittings were not included. (4) 7 days later, an airtightness test was conducted during a safety inspection. Due to an operation error of the engineering company, the hand valve remained close and the hydrogen was not supplied from the pressure vessel to the joint in question.

The INITIATING CAUSE was a loose threaded joint inside the dispenser The ROOT CAUSE was a series of mistake which did not allowed to detect the leak during maintenance inspections and tightness tests. This can be attributed to a lack of clarity in the testing procedure and shortcoming in the checklist of the operation to be performed.