Hydrogen fire in a refinery (958)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Hydrogen fire in a refinery

A hydrogen leak occurred on the hydrogen line of a hydro-desulphurisation unit, followed by ignition . The failure was located on a supply manifold of the unit at a support beam. The unit was shut down. The accident was caused by external corrosion which had developed at a support point, under the pipe insulation. A regular thinning of the piping was observed over a length of 450 mm on the lower semi-circumference. The maximum thickness loss was 6. 5 mm. The mechanical analysis concluded that the operating pressure was sufficient to cause this initial failure in the weakened area. Its propagation resulted from the dynamic load applied to the line.
Event Date
October 1, 2007
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING CAUSE was the thinning of the pipe wall caused by external, not further specified corrosion. The ROOT CAUSE is not provided, but by proxy with similar cases, it could be concluded that lack of correct non-distructive assessment system did not allow for timely detection of the loss of wall thickness due to corrosion.
Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved
hydrogen pipeline, manifold
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Lessons Learned

Undetected external corrosion of high-temperature pipe connection is a common cause of loss of confinement. The presence of a thermal insulation layers around the piping does not allow for a visual inspection of the components, and in absence of sound non-destructive assessment tools and methods, the corrosion can proceed and reduce the load-bearing section of the pipe, until the internal pressure cause it burst. Similar cases are described, among others, by events HIAD_ 1067 and HIAD_83.

Event Nature
Emergency Action
The unit was shutdown. Further emergency actions were not reported, but it is plausible that they were initiated.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Event description in the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/52695/ (accessed October 2020)