Hydrogen fire in an industrial gas production and treatment plant
A fire was caused by a hydrogen leak and led to the formation of a fireball at the end of a hose at the conditioning station. It occurred while transferring hydrogen from a stationary storage to he semi-trailer. A detonation was heard and the hydrogen supply of the site was automatically shut down by the safety devices. A plant employee had just disconnected the hose used for the filling of a semi-trailer. He did so to be able to change a non-return valve which was vibrating noisily. The hydrogen supply had been stopped, the automatic system had been switched to manual mode and the hose had been drained and disconnected. However, the anti-whip cable of the hose remained attached. Pressurized hydrogen entered the disconnected hose, causing the leak.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes