Skip to main content

hydrogen fire in the hydro-desulphurisation unit of a refinery (902)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

hydrogen fire in the hydro-desulphurisation unit of a refinery

A hot oil line (8-inch) in the hydro-desulphurisation (HDS) unit failed due to fatigue cracking. Hot oil at 50 bar and 343°C sprayed across the roadway into the hydrogen units where ignition occurred. The pipe break was a guillotine -type, probably in the heat affected zone at 2 inches from a welding. The intense fire around the pipe rack in the hydrogen plant caused a hydrogen line (16-inch) to rupture, adding a second blow torch to the fire. In successive order, more pipes ruptured with explosions. After six-and-a-half hours, the fire was extinguished. Damage was extensive. The three hydrogen units and the four HDS units were heavily damaged or destroyed.
Event Date
December 13, 1984
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause is fatigue cracking of the oil pipeline, different sources referring to probable fatigue cracking, again probably hydrogen assisted. Before the loss, the line which failed was judged as having excessive vibration. Failure of managing out-of-specification fatigue phenomena may be the root cause, or at least a contributing cause.
Facility Information
Application Type
Application
Hydrodesulphurisation process
Specific Application Supply Chain Stage
Components Involved
hydrogen (generation) unit
Storage/Process Medium
Actual Pressure
5
Location Type
Operational Condition
Pre-event Summary
9 years earlier vibrations had been noted on the gas line which failed. The structure had been stiffened by means of gussets. An hypothesis is that this intervention had amplified/accelerated the fatigue phenomena which was caused the break of the line. , together with blistering due to hydrogen attack.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Currency
Property Loss (onsite)

75000000000

Post-event Summary

Damage was extensive. The three hydrogen plants and the four HDS units were heavily damaged or destroyed. Other source report M$89(Excluding Production loss. )

Event Nature
Emergency Action
The fire lasted 6h30
Release Type
Release Substance
oil H2
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
Flame Type
References
References

Description of the event in the database ARIA https://www. aria. developpement-durable. gouv. fr/accident/7315/ (accessed September 2020)

MARSH report, 100 largest losses in the hydrocarbon industry, 27th edition 2022 https://www. marsh. com/cz/en/industries/energy-and-power/insights/100-largest-losses. html (accessed January 2024)

A. Goel, Refinery Reliability Through Advanced NDT Methodologies,Proc. National Seminar on Non-Destructive Evaluation Dec. 7 - 9, 2006, Hyderabad http://citeseerx. ist. psu. edu/viewdoc/download?doi=10. 1. 1. 216. 4819&rep=rep1&type=pdf (accessed September 2020)