Hydrogen fire at a gas production facility (989)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Hydrogen fire at a gas production facility

A leak occurred while loading a trailer carrying hydrogen gas cylinders. The trailer was loaded with 4 bundles of 60 cylinders at 200 bar which were beeing refilled. The leak was heard, and an employee closed the supply valve but the leak ignited and reached the trailer's tires. The vehicle caught fire, causing a plume of black smoke visible from a distance. The plant operator evacuated the personnel and activated the emergency response plan. The water sprayers in the filling station and the site was shut down. The firemen and the operator prevented the spread of the fire beyond the 3 other trailers parked at the loading station. After approximately 2 hours, the firemen brought the fire under control. Early in the morning of the day after approximately 10 hours from fire extinction), the fire broke out again on the tires of a semi-trailer. The firefighters used twice the firefighting flow of the first phase. After 5 hours , the firefighters finished extinguishing the semi-trailer. They checked that there were no hot spots using a thermal camera. The operator called off the emergency plan. There were no injuries but the material consequences of the fire were severe: 11 cylinders within one bundle bursted and two adjacent hydrogen trailers partially burnt. The plant operator activated a post-accident crisis unit to study how to empty the trailers from the remaining hydrogen and to purge them. (ARIA database)
Event Date
July 30, 2020
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
INITIATING CAUSE: several potential sources of hydrogen leakage were identified at the level of the trailer: either on a connection loop between a cylinder and a manifold, or on the manifold, or on a cylinder. Most probably, a small leak on fitting caused a rupture of a pigtail which induced a hydrogen jet fire, igniting the tyres and causing the cylinders to burst. ROOT CAUSE: (i) shortcoming in porcedures for maintenance and inspection of the trailer/bundles design. (ii) lack of effective prevention and mitigation measures during filling, probably related to shortcoming of the risk assessment
Facility Information
Application
CGH2 cylinders truck
Specific Application Supply Chain Stage
Components Involved
semi-trailer, hydrogen cylinders
Storage/Process Medium
Location Type
Operational Condition
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

Three semi-trailers showed significant destruction, resulting in an economic loss of 488 k€. The hydrogen conditioning installations required a repair estimated at 50 k€. The site was shut down and production was relocated. The study of the smoke plume concluded that there was no toxic effect in the vicinity of the site. The analysis of the extinguishing water shows a quality allowing its discharge into the natural environment.

Event Nature
Emergency Action
During the first fire, the fire brigade used water. During the fighting of the second fire, it used first twice the firefighting flow of the first phase. The extinguishing water was collected in a retention basin designed for this purpose, but it reached its maximum filling level. Later one, to limit the amount of water, the firemen use foam. To reduce the level of water in the basin, the operator opens its water discharge to the environment at a low rate. Firefighters set up a filtering system for the hydrocarbons. The water from the basin is then returned to the fire reserve. Finally, a thermal camera was used to ensure that there were no hot spots left.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description no 55834 in the French database ARIA (accessed October 2021)

A detailed analysis was presented by Ruban et al. at the 2023 Center for Hydrogen Safety Europe Conference The resentation is behind a paywall, but the abstract is available on line: https://proceedings. aiche. org/conferences/center-hydrogen-safety-conference-europe/2023/proceeding/paper/lessons-learned-fire-hydrogen-200-bar-filling-station (accessed January 2025)

News of 30 July of the La Voix du Nord https://www. lavoixdunord. fr/845839/article/2020-07-30/douai-incendie-en-cours-air-liquide-site-classe-seveso (accessed November 2021)