Hydrogen fire at a chlorine chemical production plant (936)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Hydrogen fire at a chlorine chemical production plant

Hydrogen fire at a chlorine chemical production plant (Seveso-classified) Hydrogen ignited in a chlorine electrolyser unit. The facility was shutdown when the incident occured. The staff of the unit, present on site, triggered the fire alarm and put the installations in a safe state. The fire was extinguished after the start of the intervention of the internal fire brigade. According to the ARIA report (see reference), a variation in electrolyser pressure was caused by the shutdown of a tank due to the malfunction of its level detection gauge. This variation caused, on one single cell, the tearing of the flexible PTFE belt whose role is to protect the cell from pressure shocks. This tearing resulted in the release of a small amount of hydrogen that spontaneously ignited. The other belts did not suffer, suggesting a structural weakness of the damaged one. These belts are regularly monitored by the operator, but their packaging during transport may have plaid a role.
Event Date
November 21, 2012
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
INITIATING CAUSE was the lose of confinement on a single cell of the chlorine electrolyser, due to an operation on a neighbouring system
Facility Information
Application Type
Application
Chlorine production
Specific Application Supply Chain Stage
Components Involved
electrolyser cells
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
The unit was shutdown.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Lessons Learned
The ARIA report (see reference) does not mention any lesson learnt. One possible corrective action, could be an improved estimation of the consequences of modifications made to part of system, for the rest of the system .
Event Nature
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event description in the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/43523/ (accessed September 2020)