Hydrogen fire in a chemical plant
The incident occurred at a hydrogenation reactor producing alcohols. At the time of the fault, the plant was in normal operation. A sudden leak of hydrogen occurred on the flange of the upper cover of a high-pressure trickle bed reactor. The escaping hydrogen ignited and a fire broke. The plant sensors for flammable gases went off in the control room a few seconds after the leak began and automatically alerted the plant fire brigade. (1) The affected part of the plant and adjacent parts were shut down using the plant shutdown switch. (2) The residual pressure in the affected hydrogenation reactor was released to the flare via the automatic rapid relief (3) The reactor was purged with nitrogen, which extinguished the flame after less than 5 minutes. (4) The BASF plant fire brigade was on site and cooled the affected parts of the plant. There were no injuries.

The INITIATING CAUSE was a hydrogen leak on a flange with a deteriorated sealing ring and a low tightening torque. The ROOT CAUSE was the failing of upgrading the correct tightening torque for this type of flanges, and the fling of inspect possible damage to the sealing ring. This can be attributed to shortcoming in the operative procedures.