European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre
Hydrocarbons and hydrogen fire in a refinery (1024)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Hydrocarbons and hydrogen fire in a refinery
During a routine inspection, a flame was observed at the bottom flange of a reactor in a refinery. Few moments later, sensors near the leak detected a rise in temperature. The facility was shut down in accordance with emergency procedures. The sprinkler system was triggered to protect the equipment. The rapid decompression of the plant towards the safety flare reduced the leak flow rapidly. One hour later, the fire was extinguished. 15,7 t of hydrocarbons were sent to the flare for burning on the day of the accident. No injuries were reported on site and no inconvenience was felt outside. The leak involved naphtha, hydrocarbon gases and hydrogen. Due to the thermal effects of the ignited leak, cables, instruments and insulation materials were damaged. [ARIA event 58577]
The INITIATING CAUSE was the leak of a process gases due to loss of sealing of a reactor flange. The leak was due to a loss of tightness at a flange, caused by an incompatibility of materials with operating conditions. The ROOT CAUSE lies in the decision of the operator to allow the replacement of a defective component with another one with different material properties. A possible additional factor could have been the absence of strict guidelines for the replacement of consumables.
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.
Contact info
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.