Hose rupture during hydrogen transfer (1138)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Hose rupture during hydrogen transfer

The incident occurred while transferring gaseous hydrogen from a tube trailer to a customer stationary supply system. The transfer hose ruptured and released hydrogen which ignited explosively. The resulting fire was allowed to “burn off” the hydrogen remaining in the trailer. The involved hose was part of system used to maintain a continuous supply to the customer. This is achieved by having one trailer kept connected as a supply source, while refilling the second trailer. By every new delivery of hydrogen, the newly refilled trailer is then connected to the customer system, before the trailer in service is isolated and disconnected. In this incident, the refilled trailer had just been connected to the customer pressure reducing station and the second trailer was in the process of being disconnected for return and refilling. While disconnecting the in-service trailer, the driver heard an unusual sound from the direction of the full trailer which had just been connected. Before he was able to investigate the source of the sound, there was an explosive ignition followed by a fire. This sequence of an explosion followed by a fire was confirmed by onsite surveillance cameras. The location of the release was the hose. There was no breach of any of the cylinders comprising the tube trailer, nor did the burst discs on any of the manifold tubes activated during the following fire. The hose was not equipped with excess flow devices, therefore the fire continued being fed by the hydrogen in the trailer, and the non-metallic components of the hose were burned. Since the whole hose was destroyed, a root cause for the incident could not be determined.

Event Date
August 26, 2010
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments

The INITIATING CAUSE was the rupture of the flexible hose. The ROOT CAUSE is unknown, the hose was destroyed during fire, and was impossible to determine the cause.

Facility Information
Application
CGH2 tube trailer
Specific Application Supply Chain Stage
Components Involved

Hose

Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary

the refilled trailer had just been connected to the customer pressure reducing station

Consequences
Number of Injured Persons
2
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

311000

Property Loss (offsite)

0

Post-event Summary

PHMSA report does not mention any injury. The online news speaks of 1 trailer operator with 2-degress burns and one Burger King customer with ear pain

Lessons Learned

An excess flow valve could be a possible measure to prevent large quantities of hydrogen to be lost when a leak occurs on a hose during hydrogen transfer. However, such a measure requires a careful design (the value of limit flow, the valve location, etc. ), a complete review of the worst failure scenarios and of the related risk assessment, to avoid introducing additional hazards (for example when a quick venting is required to reduce over-pressurisation of the storage tank).

Event Nature
Emergency Action

The resulting fire was allowed to “burn off” the hydrogen remaining in the trailer. The videos show intervention of fire brigades with water jets. The airport was shutdown for approximately 1 hour, some flights were diverted mid-air, and the roadways in the area closed. The DOT report specifies that the day after the hydrogen trailer company perofmrned a control release of the hydrogen stil in teh trailer, for a total of 25000 pounds. (approximately 1100 kg, much more than the value provided by PHMSA). It probably relates to th total capacity of two trailers. The measures was needed to be able to take away the damaged trailers.

Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
References
References

Incident I-2011010130 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: https://portal. phmsa. dot. gov/analytics/saw. dll?Portalpages&PortalPath=%2Fshared%2FPublic%20Website%20Pages%2F_portal%2FHazmat%20Incident%20Report%20Search (accessed September 2024)

U. S. Department of Transportation, Safety and Operations of Hydrogen Fuel Infrastructure in Northern Climates –- A Collaborative Complex Systems Approach Final Project Report, Grant No. DTOS59-06-G-00048 https://rosap. ntl. bts. gov/view/dot/23734/dot_23734_DS1. pdf (accessed July 2025)

Autoblog news https://www. autoblog. com/news/report-ny-hydrogen-station-used-by-gm-explodes-closes-airport (accessed July 2025)