Fire when refilling a cylinder at a hydrogen storage facility (1036)
This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.
Fire when refilling a cylinder at a hydrogen storage facility
While filling a 9 litre gas cylinder with pressurised hydrogen in the hydrogen storage area, a blast occurred which destroyed the low pressure gauge, followed by a jet fire which damaged the surface of the cylinder. The cylinder to be filled, including pressure gauge and control system, had been provided by a third party. Its nominal pressure was 35 MPa, however the maximal pressure of this filling would have been much lower, less than 20 MPa, corresponding to the maximal pressure of the bulk storage available. The pressure regulator system at the inlet of the cylinder consisted of a classic setup with a needle valve able to control the gas flow, and two pressure gauges for the high pressure (storage side) and low pressure (cylinder outlet). The blast occurred when the cylinder was approximately at 8 MPa, destroying the low-pressure gauge. The hydrogen started leaking through the damaged gauge, ignited forming a jet flame directed downwards, melting the plastic protective external layer of the gas cylinder, and probably starting damaging the carbon-reinforced epoxy layer of the cylinder.
The INITIATING CAUSE was the release and ignition of hydrogen during the filling of a small cylinder. The reason for the leak was the catastrophic failure of the pressure regulator, which created a direct connection between the high- and the low-pressure sections. How this could happen has never been clarified by the producer of the regulator or the producer of the tank assembly. It was suspected that the regulator was affected by a design weakness or a bad quality control. The ignition cause was mostly likely the electrostatic sparks generated by the metallic and glass debris produced by the mechanical failure of the pressure gauge. Other possible cause could be friction of the gas high flow through the gauge pipe. The ROOT CAUSE was the execution of an unplanned operation not covered by a specific procedure informed by a proper risk assessment. This a shared responsibility of (1) the management, which failed in supervision of technicians and in enforcing the general rules, and of (2) the technician, who decided to execute the anomalous operation without informing superiors and the safety department, and without respecting the site rules.
We are professional and reliable provider since we offer customers the most powerful and beautiful themes. Besides, we always catch the latest technology and adapt to follow world’s new trends to deliver the best themes to the market.
Contact info
We are the leaders in the building industries and factories. We're word wide. We never give up on the challenges.