Fire on two adjacent CGH2 trailers
During simultaneous hydrogen venting operations of two hydrogen trailers adjacent to one another, hydrogen was ignited at one, and then the fire ignited the hydrogen venting from the other trailer. [Ordin, NASA (1974)]
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes

The INITIATING CAUSE was presence of air in vent line, which formed an air-hydrogen explosive mixture when hydrogen was vented. The IGNITION of the hydrogen-air mixture ocurred by static charge or impact from contaminants in the vent line. Possible contributing to ignition was an inadequately grounded vent flapper. ROOT CAUSE of this incident was the simul taneous hydrogen venting from two adjacent trailers which permitted spread of the explosion. A possible inadequat design contributed to air presence in the vent.