Fire in a plastics production plant

Fire on a filter of an autoclave. The event occurred in a plant for the production of plastics. After catalytic synthesis of amines, the filter of the autoclave was taken out for cleaning. During the removal, the fire started. The fire was extinguished with water jets and water injection into the reactor vessel. The damages are very limited. The event was caused by the presence of hydrogen at the top of the reactor, which was also in contact with the filter because the valve aiming at isolation the filter had remained open. The ignition of the hydrogen is probably due to the presence of the catalyst, which is pyrophoric when dry.
Event Date
November 29, 2003
Record Quality Indicator
Region / Country
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIATING cause was the presence of hydrogen in the filter. The intermediate cause is the failing to close the valve supposed to isolate the filter from the content of the reactor. Another contributing or root cause reported is related to the procedure in place to prepare the filter for dismantling: it must be cleaned-up under water and then dried under nitrogen, to avoid the too intensive drying of the catalyst which can cause the production of sparks. In that case, the drying by nitrogen purging was longer than foreseen.
Facility Information
Application Type
Application
Plastics production
Specific Application Supply Chain Stage
Components Involved
autoclave for the synthesis of plastic
Storage/Process Medium
Location Type
Operational Condition
Pre-event Summary
After catalytic synthesis of an amine, the filter the autoclave was taken out for cleaning.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Post-event Summary

Only the filter's valve and manometer were damaged.

Event Nature
Emergency Action
The fire remained localised on the filter. The operators did not succeed in extinguishing the fire with water jets. The introduction of water directly at the entrance of the filter while closing the exit valve allowed to extinguished the fire.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Event no. 25991 of the French database ARIA (accessed December 2020)