Fire in a plastics production plant
Fire on a filter of an autoclave. The event occurred in a plant for the production of plastics. After catalytic synthesis of amines, the filter of the autoclave was taken out for cleaning. During the removal, the fire started. The fire was extinguished with water jets and water injection into the reactor vessel. The damages are very limited. The event was caused by the presence of hydrogen at the top of the reactor, which was also in contact with the filter because the valve aiming at isolation the filter had remained open. The ignition of the hydrogen is probably due to the presence of the catalyst, which is pyrophoric when dry.
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIATING cause was the presence of hydrogen in the filter. The intermediate cause is the failing to close the valve supposed to isolate the filter from the content of the reactor. Another contributing or root cause reported is related to the procedure in place to prepare the filter for dismantling: it must be cleaned-up under water and then dried under nitrogen, to avoid the too intensive drying of the catalyst which can cause the production of sparks. In that case, the drying by nitrogen purging was longer than foreseen.