Fire on a liquid hydrogen tanker
A LH2 trailer was delivering at a customer’s site. Just after having terminated the transfer to the stationary tank approximately 13000 gallons (3500 kg) of liquid hydrogen, the pressure relief valve on the trailer activated at a tank pressure of approximately 120 psig (8. 4 bar). The tanker was rated for 150 psig (9. 7 bar). The venting hydrogen ignited. The two tanks were still connected with the transfer hose. The driver immediately isolated the trailer and the customer storage tank and then called 911. The local fire department put in place an extensive emergency area, by evacuating residents and shutting down traffics. [Note of the event validator: the PHMSA source report a wrong value of 126000 cubic feet of LH2deliver in the text, but the correct value in the column dedicated to tank capacity]
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Causes
Cause Comments
The INITIAL CAUSE was the premature opening of the pressure relief valve. ROOT CAUSE is unknown. It would require a detailed investigation on the cause of material failure.