Fire on a liquid hydrogen tanker (156)

This data is from the European Hydrogen Incidents and Accidents database HIAD 2.1, European Commission, Joint Research Centre.

Fire on a liquid hydrogen tanker

A LH2 trailer was delivering at a customer’s site. Just after having terminated the transfer to the stationary tank approximately 13000 gallons (3500 kg) of liquid hydrogen, the pressure relief valve on the trailer activated at a tank pressure of approximately 120 psig (8. 4 bar). The tanker was rated for 150 psig (9. 7 bar). The venting hydrogen ignited. The two tanks were still connected with the transfer hose. The driver immediately isolated the trailer and the customer storage tank and then called 911. The local fire department put in place an extensive emergency area, by evacuating residents and shutting down traffics. [Note of the event validator: the PHMSA source report a wrong value of 126000 cubic feet of LH2deliver in the text, but the correct value in the column dedicated to tank capacity]
Event Date
April 15, 2000
Record Quality Indicator
Event Initiating System
Classification of the Physical Effects
Nature of the Consequences
Cause Comments
The INITIAL CAUSE was the premature opening of the pressure relief valve. ROOT CAUSE is unknown. It would require a detailed investigation on the cause of material failure.
Facility Information
Application
LH2 tanker
Specific Application Supply Chain Stage
Components Involved
PRD
Storage/Process Medium
Storage/Process Quantity
3500
Actual Pressure
0
Design Pressure
0
Location Type
Operational Condition
Pre-event Summary
The tanker had just terminated the transfer of LH2 to the customer's stationary tank.
Consequences
Number of Injured Persons
0
Number of Fatalities
0
Environmental Damage
0
Currency
Property Loss (onsite)

2000

Property Loss (offsite)

0

Post-event Summary

Over 300 local residents were evacuated, but no one was injured. Approximately 30 kg of hydrogen were vented to the atmosphere.

Lessons Learned

Premature activation of pressure relief devices is a regular cause of hydrogen release. It is usual due to ageing of the devices material, which could have several causes: wrong choice of the design materials, lack of inspection/maintenance, error in replacing sub-components, by not using the ones certified/specified.

Event Nature
Emergency Action
Over 300 local residents were evacuated in a a radius of 800 m. The traffic on the nearby highway stopped for 2 hours and the railway traffic was reduced, to allow the fire fighters to intervene using that area. The emergency management was performed using the EPA software CAMEO (https://www. epa. gov/cameo). Nothing is known on how that leak was stopped. Since the tanker was almost empty, it can be assumed that it was decided to let the fire extinguish by itself, and then simply driving away.
Release Type
Release Substance
H2 100%
Hydrogen Release Concentration (%)
0.00
Ignition Source
Detonation
No
Deflagration
No
High Pressure Explosion
No
High Voltage Explosion
No
References
References

Incident I-2000050966 of the US Pipeline and Hazardous Materials Safety Administration PHMSA: https://portal. phmsa. dot. gov/analytics/saw. dll?Portalpages&PortalPath=%2Fshared%2FPublic%20Website%20Pages%2F_portal%2FHazmat%20Incident%20Report%20Search (accessed September 2024)

Event description extracted from the UK database ICHEME in PDF ICHEME database is no longer available for purchase, but data can be download as PDF for free. https://www. icheme. org/knowledge/safety-centre/resources/accident-data/ (accessed October 2020)

Event nr 17608 of the French database ARIA https://www. aria. developpement-durable. gouv. fr/accident/17608/ (accessed December 2025)